Children 1st Houston / Bldg-1 / Central Plant / Chilled Water Plant
READ ONLY · DEMO SEQUENCE - NOT LIVE
GRAPHIC NOT COMMISSIONEDShowing a realistic CHW plant sequence so the operator graphic is readable; live site bindings still pending.Commands disabled until write-safety gateway is commissioned
CONDENSER LOOPCHW HEADERS →CWSCWRCHWSCHWR
POINTScmd · value · setpoint · reliability
Point
Value
SP/Cmd
Status
Trend
CH-STAT
ON / PROVEN
Enable
Missing
▣
CH-LD
64%
--
Missing
▣
CHWS
44.0°F
44.0°F
Missing
▣
CHWR
54.8°F
--
Missing
▣
CHW-DP
12.4 psid
12.0 psid
Missing
▣
CHWP-1
ON / PROVEN
Lead
Missing
▣
CHWP-1 SPD
78%
Modulate
Missing
▣
CHWP-2
STANDBY
Lag
Missing
▣
CWS
85.2°F
--
Missing
▣
CWR
94.6°F
--
Missing
▣
CWP
ON / PROVEN
Enable
Missing
▣
CT-FAN
FAN ON
Stage 1
Missing
▣
CT-BASIN
68.0°F
--
Missing
▣
Commissioning binding health:Bound 0Stale 0Demo 0Missing 14
Most slots are unbound — semantic point binding for this equipment is incomplete.