BAS Operator Drilldown

CH-2 · Water-cooled centrifugal

Trane CVHF · 350 ton · plant view: ↩ Chilled Water Plant

Read-only / advisory No BAS writes Simulated values (sim) Role: LAG Alarm active Stages: 0 / 3 running Lockouts: 1 open / 2 recent
Standby 0 % RLA (sim)

Compressor Stages

Per-compressor load and current draw. Simulated.

  • Compressor Stage 1 Off · 0 A (sim) 0 %
  • Compressor Stage 2 Off · 0 A (sim) 0 %
  • Compressor Stage 3 Off · 0 A (sim) 0 %

Evaporator

Refrigerant-side evaporator. Simulated.

Pressure
60.1 psig (sim)
Saturation Temp
35.6 °F (sim)
Approach
Flow Status
Not proven

Condenser

Refrigerant-side condenser. Simulated.

Pressure
62.0 psig (sim)
Saturation Temp
65.0 °F (sim)
Approach
Flow Status
Not proven

CHWS / CHWR Context

Plant-side chilled-water context this chiller serves. Simulated.

CHWS Temp
44.4 °F (sim)
CHWS Setpoint
44.0 °F (sim)
CHWR Temp
55.7 °F (sim)
Delta-T
Differential Pressure
12.8 psid (sim)

Lead / Lag Rotation

Read-only role display. Rotation is governed by plant logic; no BAS writes from this page.

Current Role
LAG
Rotation Note
Lag standby — auto-start on CHWS deviation > 2°F (sim)
Runtime
9,802 h (sim)
Mode
Standby

Other chillers in plant:

Lockout History / Status

Recent lockouts and trips. Open (manual reset required) listed first. Simulated.

  • 2026-05-09 11:04 L-21 · Oil pressure differential below trip threshold — manual reset required OPEN
  • 2026-05-02 22:17 L-08 · Condenser flow proof lost Auto-reset

Point / Detail Navigation

Drill into a specific point or related operator surface. Unresolved kinds render as disabled hint chips.

  • evaporator_pressure → point_detail (not yet routed)
  • condenser_pressure → point_detail (not yet routed)
  • percent_load → point_detail (not yet routed)
  • trends → trends (not yet routed)
  • alarms → alarms (not yet routed)
  • plant → chilled_water_plant

Operator Notes

Locked out: oil pressure differential trip not auto-reset.

  • Compressor stage load and current draw are visible at a glance — confirms loading order.
  • Evap/cond pressure + saturation temp pair lets the operator infer approach and refrigerant health.
  • CHWS/CHWR context ties the chiller back to the plant-level setpoint tracking question.
  • Lead/lag role is shown read-only here; rotation is plant-policy, not commanded from this page.
  • Lockout history surfaces both auto-reset events and OPEN trips that still require manual intervention.