BAS Operator Drilldown · RTU

RTU-2 · Packaged rooftop unit

Carrier WeatherMaker 50TC · 12.5 ton · back to ↩ Floor plan

Read-only / advisory No BAS writes Simulated values (sim) Unit: Off Alarm active DX: 0 / 2 on VFD fault Alarms: 1 open / 1 recent
Unoccupied · Off

Air Temperatures

Supply / return / mixed / outside air. Live BAS bindings overlay simulated values when wired.

Air-temps binding: Demo (bound=0 · stale=0 · demo=6 · missing=0)

Supply Air
Demo
Supply Setpoint
57.0 °F (sim) Demo
Discharge Setpoint
57.0 °F (sim) Demo
Return Air
79.4 °F (sim) Demo
Mixed Air
79.4 °F (sim) Demo
Outside Air
84.0 °F (sim) Demo

Supply Fan

Supply fan status and VFD feedback. Simulated.

Status
Off · VFD fault
Speed Cmd
0 % (sim)
VFD Speed
0 % (sim)
VFD Amps
0 A (sim)
VFD Fault
Overcurrent (F.OC)

DX Cooling Stages

Per-compressor DX stage status. Simulated.

  • DX Compressor 1 Off · 0 A (sim)
  • DX Compressor 2 Off · 0 A (sim)

Heating Stages

Gas-heat or electric-heat staging. Simulated.

  • Electric-heat Stage 1 Off

Outside Air / Economizer

OA damper, RA damper, economizer mode. Simulated.

OA Damper
0 % open (sim)
RA Damper
100 % open (sim)
Min OA
20 % (sim)
Economizer Mode
Disabled (unit off)
Economizer Enabled
No

Filter / Static Pressure

Filter loading and duct static pressure. Simulated.

Filter
Pleated MERV-8 filter bank
Filter ΔP
0.55 in. wc (sim)
Filter Alarm Threshold
0.90 in. wc (sim)
Filter Status
OK
Duct Static
0.00 in. wc (sim)
Duct Static SP
1.00 in. wc (sim)
Building Pressure
0.00 in. wc (sim)

Alarm History

Recent alarm/abnormal events. Open (manual reset required) listed first. Simulated.

  • 2026-05-09 06:20 VFD-OC · Supply-fan VFD overcurrent fault — manual reset required OPEN

Companion Equipment

Zones served by this RTU. Read-only links.

No companion zones declared.

Other RTUs on this floor:

Point / Detail Navigation

Drill into a specific point or related operator surface. Unresolved kinds render as disabled hint chips.

  • supply_fan_vfd → point_detail (not yet routed)
  • trends → trends (not yet routed)
  • alarms → alarms (not yet routed)
  • floor_plan → floor_plan

Operator Notes

Supply fan VFD fault — unit held off pending reset.

  • Air-temp panel pairs supply/return/mixed/outside so the operator can validate OA mixing on a packaged unit at a glance.
  • Supply-fan + VFD panel surfaces commanded speed, measured speed, amps, and fault state; VFD-fault hero chip is highlighted at the top.
  • DX cooling and heating stages are listed individually so staging order and runtime balance are visible — RTUs use staged DX, not modulating CHW.
  • Filter ΔP shows current loading vs alarm threshold so a filter-change reminder is obvious before it trips an alarm.
  • Alarm history surfaces both auto-reset events and OPEN trips that still require manual intervention.